sf6 sensor
F6 is a non dispersive infrared (NDIR) gas sensor, which is used for ambient air monitoring and adopts dual wavelength technology. It is specially designed for SF6 leakage, quality and purity analysis in gas insulated switchgear (GIS).
Rss-sf6 sensor has the characteristics of long-term stability, good repeatability, reliable performance, high precision and easy calibration
Modbus ASCII or RTU data communication provides multiple options to connect rss-sf6 sensors to the controller.
technical parameter
Measurement principle: dual wavelength, non dispersive infrared (NDIR),
Measurement range: 0-50 / 1000 / 1500ppm
Gas supply: by diffusion (atmospheric pressure)
Preheating time: < 2 minutes (startup time)
< 11 minutes (fade out complete)
< 30 minutes (full specification)
Measurement response
Response time (T90): appr. 1960s
Digital resolution (@ 0): 1ppm
Repeatability: ≤ ± 15ppm
Linear error (linear deviation): ≤ ± 20ppm
Long term stability (span): 12 months ≤ ± 30ppm
Long term stability (zero): 12 months ≤ ± 25ppm
The influence of T and P
Temperature dependence (zero): ≤ ± 1.5 ppm /℃
Temperature dependence (span): ≤ ± 3ppm /℃
Pressure dependence: the change of measured values ± 0- 100% / hPa
Electrical input and output
Power supply voltage: 6.5 v-9 V DC
Power supply current (peak value): < 140mA
Inrush current: < 600mA
Average power consumption: < 800MW
Output signal: RS485, 4-20mA
climatic conditions
Operating temperature: – 20 ° C + 40 ° C
Storage temperature: – 20 ° C + 60 ° C pressure: 800-1150 HPA
Ambient humidity: 0 – 95% RH (non condensing)
Typical values are related to 1013 HPA and 22 ℃ for drying (non condensing) and cleaning sample gases. The values do not include calibration gas tolerances.